| Model | Numberof
 channels
 | Available sensor | Input specifications | Compatible CPU module | 
| Item | Temperature input | FX5U | FX5UC | FX5UJ | FX5S | 
|   | FX5-4AD-PT-ADP | 4 ch | Usable resistance temperature detectorPt100
 Ni100
 | Inputrange
 | [Typical example]Pt100: -200 to +850˚C
 Ni100: -60 to +250˚C
 | ○Max.
 4 modules
 | ○Max.
 4 modules
 | ○Max.
 2 modules
 | ○Max.
 4 modules
 | 
| Resolution | 0.1˚C | 
|   | FX5-4AD-TC-ADP | 4 ch | ThermocoupleK, J, T,
 B, R, S
 | Inputrange
 | [Typical example]K type: -200.0 to 1200˚C
 J type: -40.0 to 750˚C
 | ○Max.
 4 modules
 | ○Max.
 4 modules
 | ○Max.
 2 modules
 | ○Max.
 4 modules
 | 
| Resolution | 0.1 to 0.3˚C(depending on the sensor used)
 | 
|   | FX5-8AD | 8 ch | Usable resistance temperature detectorPt100
 Ni100
 | Inputrange
 | [Typical example]Pt100: -200 to +850˚C
 Ni100: -60 to +250˚C
 | ○ | *1○
 | ○ | × | 
| Resolution | 0.1˚C | 
| ThermocoupleK, J, T,
 B, R, S
 | Inputrange
 | [Typical example]K type: -270.0 to 1200˚C
 J type: -40.0 to 750˚C
 | 
| Resolution | 0.1 to 0.3˚C(depending on the sensor used)
 | 
|   | FX5-4LC | 4 ch | Platinum resistance thermometer sensorPt100, JPt100, Pt1000
 | Inputrange
 | [Typical example]3-wire Pt100: -200 to 600˚C
 3-wire JPt100: -200 to 500˚C
 2-wire/3-wire Pt1000: -200.0 to 650.0˚C
 | ○ | *1○
 | ○ | × | 
| Resolution | 0.1˚C or 1˚C(depending on the sensor used)
 | 
| ThermocoupleK, J, R, S,
 E, T, B, N JIS C 1602-1995,
 PLⅡ, W5Re/W26Re, U, L
 | Inputrange
 | [Typical example]K type: -200.0 to 1300˚C
 J type: -200.0 to 1200˚C
 | 
| Resolution | 0.1˚C or 1˚C(depending on the sensor used)
 | 
| Micro voltage input | Inputrange
 | 0 to 10 mV DC0 to 100 mV DC
 | 
| Resolution | 0.5 μV or 5.0 μV(depending on the sensor used)
 | 
|   | FX3U-4LC | 4 ch | Platinum resistance thermometer sensorPt100, JPt100, Pt1000
 | Inputrange
 | [Typical example]3-wire Pt100: -200 to 600˚C
 2-wire/3-wire Pt1000: -200.0 to 650.0˚C
 | *2○
 Max.
 6 to 8
 modules
 *3
 | *2○
 Max.
 6 modules
 | × | × | 
| Resolution | 0.1˚C or 1˚C(depending on the sensor used)
 | 
| ThermocoupleK/J/R/S/E/T/B/
 N/PLII/W5Re/
 W26Re/U/L type
 | Inputrange
 | [Typical example]K type: -200.0 to 1300˚C
 J type: -200.0 to 1200˚C
 | 
| Resolution | 0.1˚C or 1˚C(depending on the sensor used)
 | 
| Low voltage input | Inputrange
 | 0 to 10 mV DC0 to 100 mV DC
 | 
| Resolution | 0.5 μV or 5.0 μV(depending on the sensor used)
 |