| Range of product | Harmony XB5R |
|---|---|
| Product or component type | Wireless and batteryless range |
| Device short name | ZBRA |
| Product destination | Wireless Schneider Electric ecosystem devices |
| Control station application | Transceiver (emission and reception) |
| Colour of base of enclosure | Black (RAL 9011) |
| Colour of cover | Transparent |
| Material | Polycarbonate |
| frequency | 2405 MHz for transmitter 2405 MHz for receiver |
| emission class | 5M00G7W |
| Antenna type | Omnidirectional |
| Communication port protocol | Zigbee green power at 2.4 GHz conforming to IEEE 802.15.4 |
|---|---|
| Antenna gain | 0 dBi |
| Maximum sensing distance | 300 m transmitter in box type XAL D, receiver in metal enclosure and use relay-antenna |
| maximum emission power | 3 mW |
| [Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz - 10...10 % |
| Maximum power consumption in W | 4 W AC/DC |
| Operating position | Vertical |
| Status LED | 1 LED green for power ON 1 LED green for emission signal |
| Overvoltage category | III conforming to IEC 60664-1 |
| Rated short-duration power frequency withstand voltage | 4 kV 50 Hz conforming to IEC 60947-5-1 |
| [Uimp] rated impulse withstand voltage | 4 kV |
| Electrical connection | 2 conductors cable 0.34 mm² - flexible - 5 m conforming to IEC 60947-1 |
| Tightening torque | 0.6 N.m conforming to IEC 60947-1 |
| Housing material | Self-extinguishing plastic |
| Short-circuit protection | 0.4 A fuse type fast blow |
| Max power consumption in W | 1 mW |
| number of channels | 1 |
| modulation technique | O-QPSK |
| Bandwidth | 5 MHz |
| Net weight | 0.2 kg |
| Ambient air temperature for storage | -40…70 °C |
|---|---|
| Relative humidity | 90 % at -20…55 °C, without condensation conforming to ETSI EN 300 440-1 |
| Electrical shock protection class | Class II conforming to IEC 61140 |
| IP degree of protection | IP65 conforming to IEC 60529 55 °C 0.1 m |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IK degree of protection | IK03 conforming to IEC 62262 |
| Radio agreement | RSS SRRC ANATEL, type III conforming to ETSI EN 301 489-3 ARIB T66, class 2 conforming to ETSI EN 301 489-3 FCC, category 2 conforming to ETSI EN 300 440-1 ICASA, category 1 conforming to ETSI EN 300 440-1 |
| product certifications | CCC BT 2006/95/EC UL GOST CSA CE C-Tick |
| Directives | 1999/5/EC - R&TTE directive 2004/108/EC - electromagnetic compatibility |
| Vibration resistance | +/-0.5 mm (f= 10…55 Hz) conforming to IEC 60068-2-6 6 gn (f= 55…150 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 25 gn (duration = 6 ms) for 6000 shocks conforming to IEC 60068-2-27 15 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27 |
| Insulation resistance | > 500 MOhm at 500 V DC conforming to NF C 20030 |
| [Ui] rated insulation voltage | 250 V conforming to IEC 60664-1 |
| Electromagnetic compatibility | Immunity for industrial environments conforming to IEC 61000-6-2 Conducted and radiated emissions class B conforming to CISPR 22 Electrostatic discharge immunity test - test level: 8 kV (in free air (in insulating parts)) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (on contact (on metal parts)) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80...2000 MHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 3 V/m (80...2700 MHz, distance = 20 m) conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test - test level: 2 kV conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test - test level: 1 kV (differential mode) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (common mode) conforming to IEC 61000-4-5 Conducted RF disturbances - test level: 10 V conforming to IEC 61000-4-6 Immunity to microbreaks and voltage drops conforming to IEC 61000-4-11 Radiated emission conforming to ETSI EN 300 440-1 Conducted emission conforming to EN 300-489-1 Conducted emission conforming to ETSI EN 300 489-3 Radiated emission conforming to ETSI EN 300 440-2 |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.000 cm |
| Package 1 Width | 8.000 cm |
| Package 1 Length | 18.700 cm |
| Package 1 Weight | 267.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 18 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.293 kg |